RD6MGSS – Rytons Stainless Steel Cowled Meshed Grille (150mm Dia. Range)
- Home
- 150mm (220mm x 90mm) RytDuct Flat Channel Duct
- External Grilles 220mm x 90mm – 150mm Dia.
- RD6MGSS - Rytons Stainless Steel Cowled Meshed Grille (150mm Dia. Range)
RD6MGSS – Rytons Stainless Steel Cowled Meshed Grille (150mm Dia. Range)
- General Details
- Quote Request
- Related Products
General Details
- Stainless steel bull-nosed terminal with wire grille and spigot for 150mm dia. rigid pipe and flexible ducting.
- Connects to Rigid Pipe RD636RND and suits 150mm dia. RytHose range (or use RD6HC).
- A durable and stylish alternative to a plastic grille.
- For use in areas requiring lower extraction rates such as bathrooms, kitchens and utility rooms.
- Operating temperatures -15ºC to 60ºC.
Size:
- 213mm Dia. flange x 100mm D with 145mm Dia. male spigot.
Free Area:
- 15,065mm² per unit.
Composition:
- Stainless Steel (Grade 304).
Associated Ducting:
Airflow and Resistance:
- 8 l/s: 0.6 Pa.
- 13 l/s: 2.12 Pa.
- 21 l/s: 5.96 Pa.
- 30 l/s: 12.34 Pa.
- 60 l/s: 49.42 Pa.
- 120 l/s: 196.46 Pa.
Reference Material:
- The Building Regulations F1 2021, Installation of ventilation systems, 1.80. Each air terminal should have a free area of at least 90% of the free area of its associated duct.
- Note: This approved document takes effect on 15 June 2022 for use in England. It does not apply to work subject to a building notice, full plans application or initial notice submitted before that date, provided the work is started on site before 15 June 2023.
Handling Information:
- Weight: 402g.
Rytons is proud to be a family run business and British manufacturer since 1972